GSO IEC 60947-4-1:2016
IEC 60947-4-1:2009
Gulf Standard
Historical
·
Approved on
07 April 2016
Low-voltage switchgear and controlgear - Part 4-1: Contactors and motor-starters - Electromechanical contactors and motor-starters
GSO IEC 60947-4-1:2016 Files
English
250 Pages
Historical
Reference Language
Obtaining this standard through the store is currently unavailable. You can acquire it directly from its source.
GSO IEC 60947-4-1:2016 Scope
IEC 60947-4-1:2009+A1:2012 applies to the types of equipment whose main contacts are intended to be connected to circuits the rated voltage of which does not exceed 1 000 V a.c. or 1 500 V d.c. Starters and/or contactors dealt with in this standard are not normally designed to interrupt short-circuit currents. Therefore, suitable short-circuit protection forms part of the installation but not necessarily of the contactor or the starter. This third edition replaces the second edition published in 2000 and its Amendments 1 (2002) and 2 (2005). It is a technical revision. This edition includes the following significant technical changes with respect to the previous edition (2000) and its Amendments 1 (2002) and 2 (2005):
- deletion of the test at -5 °C and +20 °C for thermal overload relays that are not compensated for ambient air temperature;
- addition of conditions of the tests according to Annex Q of IEC 60947-1;
- EMC tests: clarification of acceptance criteria and alignment with IEC 60947-1 for fast transient severity level;
- Annex B, test for Icd: modification of the duration of the dielectric test voltage from 5 s to 60 s;
- Annex B, electrical durability: improvement of the statistical aspects;
- Annex H: clarification and introduction of new extended functions within electronic overload relays;
- Annex K, procedure to determine data for electromechanical contactors used in functional safety applications: creation of this new annex. This standard shall be read in conjunction with IEC 60947-1, Low voltage switchgear and controlgear - Part 1: General rules. The provisions of the general rules are applicable to this standard, where specifically called for. This consolidated version consists of the third edition (2009) and its amendment 1 (2012). Therefore, no need to order amendment in addition to this publication.
This publication shall be read in conjunction with IEC 60947-1:2007.
Best Sellers From Electrical Sector
YSMO GSO 2530:2023
GSO 2530:2016
Yemeni Technical Regulation
Energy Labelling And Minimum Energy Performance Requirements For Air-Conditioners
GSO 2530:2016
Gulf Standard
Energy Labelling And Minimum Energy Performance Requirements For Air-Conditioners
GSO 34:2007
Gulf Technical Regulation
LEAD-ACID STARTER BATTERIES USED FOR
MOTOR VEHICLES AND INTERNAL
COMBUSTION ENGINES
GSO 35:2007
Gulf Standard
Methods of test
for lead-acid starter batteries used for motor vehicles
and internal combustion engines
Recently Published from Electrical Sector
GSO 2693:2026
Gulf Technical Regulation
The GCC Terrestrial Radio Receiver Specifications for AM/FM/T-DAB+
GSO IEC 60335-2-6:2026
IEC 60335-2-6:2024
Gulf Standard
Household and similar electrical appliances - Safety - Part 2-6: Particular requirements for stationary cooking ranges, hobs, ovens and similar appliances
GSO IEC 60335-2-27:2026
IEC 60335-2-27:2024
Gulf Standard
Household and similar electrical appliances - Safety - Part 2-27: Particular requirements for appliances for skin exposure to optical radiation
GSO IEC 61557-14:2026
IEC 61557-14:2023
Gulf Standard
Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 14: Equipment for testing the safety of electrical equipment of machinery